Function Of Binary Input Signals - Toshiba GRE110 Instruction Manual

Overcurrent protection relay
Table of Contents

Advertisement

Functions
OC1 protection block
OC2 protection block
OC3 protection block
OC4 protection block
EF1 protection block
EF2 protection block
EF3 protection block
EF4 protection block
SEF1 protection block
SEF2 protection block
SEF3 protection block
SEF4 protection block
Undercurrent protection block
Thermal overload protection block
Negative sequence OC block
Broken conductor protection
Trip circuit supervision
CB open state monitoring
CB close state monitoring
Breaker failure protection initiate
Breaker failure protection initiate
Breaker failure protection initiate
Breaker failure protection initiate
Indication remote reset
Synchronize clock
Disturbance record store
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Remote open command
Remote close command
Interlock
(*1) : Signal names are those used in the scheme logic / LCD indication.
The binary input signals can be programmed to switch between two settings groups.
Table 3.2.2 Function of Binary Input Signals
Signal Names (*1)
OC1 BLOCK / OC1BLK
OC2 BLOCK / OC2BLK
OC3 BLOCK / OC3BLK
OC4 BLOCK / OC4BLK
EF1 BLOCK / EF1BLK
EF2 BLOCK / EF2BLK
EF3 BLOCK / EF3BLK
EF4 BLOCK / EF4BLK
SEF1 BLOCK / SEF1BLK
SEF2 BLOCK / SEF2BLK
SEF3 BLOCK / SEF3BLK
SEF4 BLOCK / SEF4BLK
UC BLOCK / UCBLK
THM BLOCK / THMBLK
NPS BLOCK / NPSBLK
BCD BLOCK / BCDBLK
TC FAIL / TCFALM
CB CONT OPN / CBOPN
CB CONT CLS / CBCLS
EXT TRIP3PH / EXT3PH
EXT TRIP-APH / EXTAPH
EXT TRIP-BPH / EXTBPH
EXT TRIP-CPH / EXTCPH
REMOTE RESET / RMTRST
SYNC CLOCK / SYNCLK
STORE RECORD / STORCD
Alarm 1 / Alarm1
Alarm 2 / Alarm2
Alarm 3 / Alarm3
Alarm 4 / Alarm4
REMOTE OPEN / RMTOPN
REMOTE CLOSE / RMTCLS
Control Lock / CNTLCK
 67 
6 F 2 T 0 1 7 2
Driving Contact Condition
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Closed to block
Trip supply
CB normally open contact closed
CB normally close contact closed
External trip - 3 phase.
External trip - A phase.
External trip - B phase
External trip - C phase
Closed to reset TRIP LED indication
and latch of binary output relays
Synchronize clock
Closed to store the record
Closed to display Alarm 1 text.
Closed to display Alarm 2 text.
Closed to display Alarm 3 text.
Closed to display Alarm 4 text.
Close to output CB open command.
Close to output CB close command.
Close to block CB close command.