Toshiba GRE110 Instruction Manual page 239

Overcurrent protection relay
Table of Contents

Advertisement

Menu
Name
SEF
Protection
THM
NPS
BCD
Range
SE1-k
0.00 – 300.00
0.00 – 5.00
SE1-α
SE1-C
0.000 – 5.000
SE1-kr
0.00 – 300.00
SE1-β
0.00 – 5.00
SE2
0.001 – 0.250 A
TSE2
0.010 – 1.500
TSE2
0.00 – 300.00 s
TSE2R
0.0 – 300.0 s
TSE2RM
0.010 – 1.500
SE2-k
0.00 – 300.00
0.00 – 5.00
SE2-α
SE2-C
0.000 – 5.000
SE2-kr
0.00 – 300.00
0.00 – 5.00
SE2-β
SE3
0.001 – 0.250 A
TSE3
0.00 – 300.00 s
SE4
0.001 – 0.250 A
TSE4
0.00 – 300.00 s
THM
0.40 – 10.00 A
THMIP
0.00 – 5.00 A
TTHM
0.5 – 500.0 min
THMA
50 – 99 %
NPS1
0.10 – 10.00 A
TNPS1
0.00 – 300.00 s
NPS2
0.10 – 10.0 A
TNPS2
0.00 – 300.00 s
BCD
0.10 – 1.00 A
TBCD
0.00 – 300.00 s
Contents
Configurable
IDMT
Curve setting
(if MSE1=C)
SEF2 Threshold
SEF2 Time
multiplier
(if MSE2≠D)
SEF2 Definite time
(if MSE2=D)
SEF2 Definite
time reset delay
(if SE2R=DEF)
SEF2 Dependent
time reset time
(if SE2R=DEP)
Configurable
IDMT
Curve setting
(if MSE2=C)
SEF3 Threshold
SEF3 Definite time
SEF4 Threshold
SEF4 Definite time
Thermal Overload
Prior load(Test)
Thermal heating
Time Constant
Thermal Alarm
NPS1 Threshold
NPS1
Definite time
NPS2 Threshold
NPS2
Definite time
Broken Conductor
Threshold
Broken Conductor
Definite time
 240 
6 F 2 T 0 1 7 2
Default
-- (0.14)
-- (0.02)
-- (0.000)
-- (2.00)
-- (2.00)
-- (0.500)
-- (1.000)
-- (0.00)
-- (0.0)
-- (1.000)
-- (0.14)
-- (0.02)
-- (0.000)
-- (2.00)
-- (2.00)
-- (0.500)
-- (0.00)
-- (0.500)
-- (0.00)
1.00A
0.00A
10.0min
80%
0.40A
0.00s
0.20A
0.00s
0.20A
0.00s