Toshiba GRE110 Instruction Manual page 36

Overcurrent protection relay
Table of Contents

Advertisement

Element
Range
UC1
0.10 – 10.0 A
TUC1
0.00 – 300.00 s
UC2
0.10 – 10.0 A
TUC2
0.00 – 300.00 s
[UC1EN]
Off / On
[UC2EN]
Off / On
Step
Default
0.01 A
0.40 A
0.01 s
0.00 s
0.01 A
0.20 A
0.01 s
0.00 s
Off
Off
 35 
6 F 2 T 0 1 7 2
Remarks
UC1 threshold setting
UC1 definite time setting
UC2 threshold setting
UC2 definite time setting
UC1 Enable
UC2 Enable

Hide quick links: