Pixit For Data Set Model; Pixit For Substitution Model; Pixit For Setting Group Control Model - Toshiba GRE110 Instruction Manual

Overcurrent protection relay
Table of Contents

Advertisement

PIXIT for Data set model

ID
Description
Ds1
What is the maximum number of data
elements in one data set (compare ICD
setting)
Ds2
How many persistent data sets can be
created by one or more clients
(this
number
datasets)
Ds3
How many non-persistent data sets
can be created by one or more clients

PIXIT for Substitution model

ID
Description
Sb1
Are substituted values stored in
volatile memory?

PIXIT for Setting group control model

ID
Description
Sg1
What is the number of supported
setting groups for each logical device
(compare NumSG in the SGCB)
Sg2
What is the effect of when and how the
non-volatile storage is updated
(compare IEC 61850-8-1 $16.2.4)
Sg3
Can multiple clients edit the same
setting group
Sg4
What happens if the association is lost
while editing a setting group
Sg5
Is EditSG value 0 allowed?
includes
predefined
 334 
Value / Clarification
Not limited by an internal configuration
parameter.
This IED does not have CreateDataSet
service. But any DataSet can be defined by
using engineering tool. The maximum number
depends on the memory size of IED.
Not limited by an internal configuration
parameter.
The maximum number depends on the
memory size of IED.
N.A.
Value / Clarification
N.A.
Value / Clarification
2
Just
SelectActiveSG
supported according to PICS.
After changing setting group number with
LCD panel, you can see new setting group
with GetSGCBValue service.
N.A.
N.A.
N.A.
6 F 2 T 0 1 7 2
service
will
be

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents