Dimensions; Power Supply; Side View Of Gre110 With The Mounting Attachment Kit Positions; Rear View Of Gre110 With Tighten The Screw Of The Mounting Attachment Kits - Toshiba GRE110 Instruction Manual

Overcurrent protection relay
Table of Contents

Advertisement

6 F 2 T 0 1 7 2
Fig. 5.2.2 Side view of GRE110 with the mounting attachment kit positions
(a) model 400A, 401A, 420A, 421, 820 and 821A
(b) model 402A and 422A
Fig. 5.2.3 Rear view of GRE110 with tighten the screw of the mounting attachment kits

5.2.2 Dimensions

5.2.2.1 Power Supply

The power supply for the relay can be either DC (range 24-48Vdc, 48-110Vdc, 110-250Vdc) or
AC (110-220Vac-50/60Hz). The voltage range is specified on the relay indicator plate on the front
face. On models 400A, 401A, 420A 421A, 820A and 821A, the power supply should be connected
to terminals 13 and 14 of TB1 and the earthing should be connected to terminal 12 of TB1.
On models 402A and 422A, the power supply should be connected to terminals 13 and 14 of TB2
and the earthing should be connected to terminal 12 of TB2.
2
A minimum 1.25mm
wire size recommended.
 155 