Toshiba GRE110 Instruction Manual page 345

Overcurrent protection relay
Table of Contents

Advertisement

2. CB remote control
To control the CB at remote site with the IEC 61850 communication, do the following.
・Operation item
- Remote control by the Select Before Operate or Direct Operate (CB Open / CB Close)
- Change of interlock position (BlkOpn or BlkCls)
- Trip LED reset
・Operating procedure
To control the CB at remote site with ICE 61850 communication is require the following three steps.
- get Logical nodes by using IEC 61850 data setting tools (such as TAMARACK tool).
- change the control logical node (XCBR, CILO or CSWI).
When CB is remote controlled from PC, showing below the control reaction depending on the CB Status.
CB Status
BI-a
BI-b
(CB_OPC_BI)
(CB_CLC_BI)
0
0
1
0
1
1
0
1
※Lock condition is as follows.
Setting the Inter lock in the Control screen of front panel LCD (see chapter 4.2.6.11) and remote
setting the CB open lock and CB close lock from PC.
Occurring Relay Trip.
When Local/Remote status is "Local" (see chapter 4.2.7.1).
When Control status is "Disable" (see chapter 4.2.6.11).
CB LED
CB Open Operation
lighting
・Unlock: operate
CLOSE
: not operate
・Lock
・Unlock: operate
CLOSE
・Lock: not operate
・Unlock: not operate
CLOSE
・Lock: not operate
・Unlock: not operate
OPEN
・Lock: not operate
 346 
Response
CB Close Operation
・Unlock: not operate
・Lock: not operate
・Unlock: not operate
・Lock: not operate
・Unlock: not operate
・Lock: not operate
・Unlock: operate
・Lock: not operate
6 F 2 T 0 1 7 2