Toshiba GRE110 Instruction Manual page 294

Overcurrent protection relay
Table of Contents

Advertisement

INF
Description
Selection of standard information numbers in control direction
System functions
Initiation of general
0
interrogation
0
Time synchronization
General commands
16
Auto-recloser on/off
17
Teleprotection on/off
18
Protection on/off
19
LED reset
23
Activate characteristic 1
24
Activate characteristic 2
25
Activate characteristic 3
26
Activate characteristic 4
Generic functions
Read headings of all defined
240
groups
Read values or attributes of
241
all entries of one group
Read directory of a single
243
entry
Read values or attributes of a
244
single entry
General Interrogation of
245
generic data
248 Write entry
249 Write entry with confirmation
250 Write entry with execution
251 Write entry abort
Note (∗4): When the relay is receiving the "Protection off" command, the " IN SERVICE LED" is off.
Description
Basic application functions
Test mode
Blocking of monitor direction
Disturbance data
Generic services
Private data
Miscellaneous
Measurand
Current L1
Current L2
Current L3
Voltage L1-E
Voltage L2-E
Voltage L3-E
Active power P
Reactive power Q
Frequency f
Voltage L1 - L2
Contents
(*4)
Reset indication of latched LEDs.
Setting Group 1
Setting Group 2
Setting Group 3
Setting Group 4
Contents
Ia
Ib
Ic
Va
Vb
Vc
P
Q
f
Vab
 295 
Type
COM
ID
--
7
--
6
ON/OFF
20
Not supported
ON/OFF
20
ON
20
ON
20
ON
20
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
GRE110
Comment
supported
Yes
Yes
No
No
No
Max. MVAL = rated
value times
1,2 or 2,4
IECNFI setting
1,2 or 2,4
IECNFI setting
1,2 or 2,4
IECNFI setting
No
No
No
No
No
No
No
6 F 2 T 0 1 7 2
COT FUN
9
160
8
160
20
160
20
160
20
160
20
160
20
160

Hide quick links: