Toshiba GRE110 Instruction Manual page 34

Overcurrent protection relay
Table of Contents

Advertisement

Element
Range
TSE1S2
0.00 – 300.00 s
SE2
0.001 – 1.000 A
TSE2
0.00 – 300.00 s
TSE2M
0.010 – 1.500
TSE2R
0.0 – 300.0 s
TSE2RM
0.010 – 1.500
SE3
0.001 – 1.000 A
TSE3
0.00 – 300.00 s
SE4
0.001 – 1.000 A
TSE4
0.00 – 300.00 s
ZP
0.00 – 25.00 W
[SE1EN]
Off / On
[SE1-DIR]
FWD / REV / NON
[MSE1]
D/IEC/IEEE/US/C
[MSE1C]
MSE1C-IEC
NI / VI / EI / LTI
MSE1C-IEEE
MI / VI / EI
MSE1C-US
CO2 / CO8
[SE1R]
DEF / DEP
[SE1S2]
Off / On
[VTF-SE1BLK]
Off / On
[SE2EN]
Off / On
[SE2-DIR]
FWD / REV /NON
[MSE2]
D/IEC/IEEE/US/C
[MSE2C]
MSE2C-IEC
NI / VI / EI / LTI
MSE2C-IEEE
MI / VI / EI
MSE2C-US
CO2 / CO8
[SE2R]
DEF / DEP
[VTF-SE2BLK]
Off / On
[SE3EN]
Off / On
[SE3-DIR]
FWD / REV / NON
[VTF-SE3BLK]
Off / On
[SE4EN]
Off / On
[SE4-DIR]
FWD / REV / NON
[VTF-SE4BLK]
Off / On
[ZPEN]
Off / On
Step
Default
0.01 s
1.00 s
0.001 A
0.010 A
0.01 s
1.00 s
0.001
1.000
0.1 s
0.0 s
0.001
1.000
0.001 A
0.100 A
0.01 s
1.00 s
0.001 A
0.500 A
0.01 s
0.00 s
0.01 W
0.00 W
Off
FWD
D
NI
MI
CO2
DEF
Off
Off
Off
FWD
D
NI
MI
CO2
DEF
Off
Off
FWD
Off
Off
FWD
Off
Off
 33 
6 F 2 T 0 1 7 2
Remarks
SEF1 stage 2 definite time setting
SEF2 threshold setting
SEF2 definite time setting. Required if
[MSE2] = D.
SEF2 inverse time multiplier setting.
Required if [MSE2] = IEC, IEEE or US.
SEF2 definite time delayed reset. Required
if [MSE2] = IEC or [SE1R] = DEF.
SEF2 dependent time delayed reset time
multiplier. Required if [SE2R] = DEP.
SEF3 threshold setting
SEF3 definite time setting.
SEF4 threshold setting
SEF4 definite time setting.
Zero phase sequence power sensitivity
SEF1 Enable
SEF1 directional characteristic
SEF1 characteristic
SEF1 inverse curve type.
Required if [MSE1] = IEC.
Required if [MSE1] = IEEE.
Required if [MSE1] = US.
SEF1 reset characteristic. Required if
[MSE1] = IEEE or US.
SEF1 stage 2 timer enable
VTF block enable
SEF2 Enable
SEF2 directional characteristic
SEF2 characteristic
SEF2 inverse curve type.
Required if [MSE2] = IEC.
Required if [MSE2] = IEEE.
Required if [MSE2] = US.
SEF2 reset characteristic. Required if
[MSE2] = IEEE or US.
VTF block enable
SEF3 Enable
SEF3 directional characteristic
VTF block enable
SEF4 Enable
SEF4 directional characteristic
VTF block enable
Zero phase sequence power block enable

Hide quick links: