Toshiba GRE110 Instruction Manual page 231

Overcurrent protection relay
Table of Contents

Advertisement

Menu
Name
Active gp.
AOLED
Active
Control
group /
Common
Interlock
Control Hierarchy
Frequency
Line name
OCCT
EFCT
SEFCT
VEVT
SVCNT
Protection
OC
Range
1 - 2
Off / On
Disable / Enable
Disable / Enable
Local / Remote
50Hz / 60Hz
Specified by user
1 – 20000
1 – 20000
1 – 20000
1 – 20000
ALM&BLK / ALM
OC1EN
Off / On
D / IEC / IEEE /
MOC1
US / C
MOC1C
NI / VI / EI / LTI
- IEC
MOC1C-
MI / VI / EI
IEEE
MOC1C-
CO2 / CO8
US
OC1R
DEF / DEP
OC1-2F
NA / Block
Contents
Active setting group
ALARM LED
lighting control
at alarm output
Control Enable
Interlock Enable
Control Hierarchy
(if Control = Enable)
Frequency
Line name
CT ratio of
Phase CT
CT ratio of
Earth Fault CT
CT ratio of
Sensitive
Earth Fault CT
VT ratio for
Sensitive
Earth Fault function
AC input imbalance
OC1 Enable
OC1 Delay Type
(if OC1EN=On)
OC1 IEC
Inverse Curve Type
(if MOC1=IEC)
OC1 IEEE
Inverse Curve Type
(if MOC1=IEEE)
OC1 US
Inverse Curve Type
(if MOC1=US)
OC1 Reset
characteristic.
(if MOC1=
IEEE,US or C)
OC1 2f Block
Enable
 232 
6 F 2 T 0 1 7 2
Default
1
On
Enable
Disable
-- (Local)
50Hz
400
200
-- (400)
-- (1)
ALM&
BLK
On
D
NI
MI
CO2
DEF
NA

Hide quick links:

Advertisement

Table of Contents
loading