X500, X501: DRIVE-CLiQ interface
Table 4- 34
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
X524: Electronic power supply
Table 4- 35
Max. connectable cross-section: 2.5 mm²
The maximum cable length that can be connected is 10 m.
Note
The two "+" and "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
The current consumption increases by the value for the DRIVE-CLiQ participant and digital
outputs.
Note
The terminal block must be screwed on tightly using a flat-bladed screwdriver.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
DRIVE-CLiQ interface X500 and X501
Pin
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
Terminal block X524
Terminal
Function
+
Electronic power
supply
+
Not assigned
M
Electronics ground
M
Electronics ground
Signal name
Voltage: 24 V DC (20.4 to 28.8 V)
Current consumption: max. 1.0 A
(without DRIVE-CLiQ or digital outputs)
Max. current via jumper in connector: 20 A (15 A
according to UL/CSA)
Electrical installation
4.10 Signal connections
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
Technical data