Siemens SINAMICS G130 Operating Instructions Manual page 372

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Output terminals
8.2 TM31 analog outputs
Scaling
Table 8- 2
Scaling
Size
Reference speed
Reference voltage
Reference current
Reference torque
Reference power
Reference frequency
Reference modulation depth
Reference flux
Reference temperature
Example: changing analog output 0 from voltage to current output 0 ... 20 mA
Example: changing analog output 0 from voltage to current output 0 ... 20 mA and setting the
characteristic
372
Scaling parameter
100 % = p2000
100 % = p2001
100 % = p2002
100 % = p2003
100 % = r2004
100 % = p2000/60
100 % = Maximum output voltage without over-
load
100 % = Rated motor flux
100% = p2006
Current output present at terminal 3, ground is at terminal 2
Set analog output type 0 to 0 ... 20 mA.
Current output present at terminal 3, ground is at terminal 2
Set TM31.AO_type [analog output 0] to 0 ... 20 mA.
Set TM31.AO_char. x1 to 0.00%.
Default for quick commissioning
p2000 = Maximum speed (p1082)
p2001 = 1000 V
p2002 = Current limit (p0640)
p2003 = 2 x rated motor torque
r2004 = (p2003 x p2000 x π) / 30
p2006 = 100°C
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A