Table 12- 13 Power Module, 660 ... 690 V 3 AC, Part 2
Article number
Unit rating
- for I
at 50 Hz and 690 V
L
- for I
at 50 Hz and 690 V
H
Output current
- Rated current I
N
- Base load current I
2)
L
- Base load current I
3)
H
Input current
- Rated input current
- Input current, max.
- Current for 24 V DC auxiliary supply
Supply voltages
- Line voltage
- Electronic power supply
- Output voltage
Power loss
Cooling air requirement
Max. cable length
between Power Module and motor
- shielded
- unshielded
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line connection (U1, V1, W1)
Connection cross-section, max. (IEC)
Motor connection
(U2/T1, V2/T2, W2/T3)
Connection cross-section, max. (IEC)
PE1 / GND connection
Connection cross section, max. (IEC)
PE2 / GND connection
Connection cross section, max. (IEC)
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight, approx.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
6SL3310-
kW
1)
kW
1)
A
A
A
A
A
A
4)
V
ACrms
V
DC
V
ACrms
kW
m³/s
m
m
dB(A)
mm
2
mm
2
mm
2
mm
2
mm
mm
mm
kg
1GH31-5AAx
1GH31-8AAx
132
160
110
132
150
175
142
171
134
157
164
191
232
279
0.8
0.9
660 to 690 V 3 AC ±10 % (-15 % < 1 min)
24 (20.4 to 28.8)
0 V 3 AC to line voltage
2.5
3.8
0.17
0.36
300
300
450
450
64/67
69/73
Screw M10
Screw M10
2 x 185
2 x 240
Screw M10
Screw M10
2 x 185
2 x 240
Screw M10
Screw M10
2 x 185
2 x 240
Screw M10
Screw M10
2 x 185
2 x 240
IP20
IP20
326
326
1400
1533
356
545
FX
GX
104
176
Technical specifications
12.3 Technical specifications
1GH32-2AAx
200
160
215
208
192
224
341
0.9
4.8
0.36
300
450
69/73
Screw M10
2 x 240
Screw M10
2 x 240
Screw M10
2 x 240
Screw M10
2 x 240
IP20
326
1533
545
GX
176
577