Unpacking - Siemens SINAMICS G130 Operating Instructions Manual

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Mechanical installation
3.3 Assembly
Installation is realized in accordance with the dimension drawings supplied. The clearance to
be maintained around the units is also specified on the dimension drawings.
The cooling air for the power unit is drawn from the lower part of the device. The warmed air
is expelled through the heat sink. When installing the device in cabinet units, you must
ensure that suitable barriers are in place to ensure that the warmed air is not drawn back into
the suction area of the heat sink.
According to EN 61800-3, the built-in unit is not suitable for use in low-voltage public
networks that supply residential buildings. High-frequency interference may occur if it is used
in this type of line supply.
Through additional measures (e.g. line filter) operation is possible in the "First environment"
in accordance with EN 61800-3 Category C2.
Note
Radio service interference due to high frequency (radio frequency) disturbances
The converter can cause high frequency disturbances, which may make interference
suppression measures necessary.
This device is not designed for general use in the first environment (residential area) and
must not be used there without appropriate radio interference suppression measures.
• Have the installation and commissioning with appropriate radio interference suppression
measures preformed by qualified personnel.
3.3.2

Unpacking

Check the delivery against the delivery note to ensure that all the items have been delivered.
Check that the devices are intact.
The packaging material must be disposed of in accordance with the applicable country-
specific guidelines and rules.
3.3.3
Required tools
You require the following tools for installation:
● Standard set of tools with screwdrivers, screw wrenches, socket wrenches, etc.
● Torque wrenches 1.5 Nm to 100 Nm
● 600 mm extension for socket wrenches