Functions, monitoring, and protective functions
9.3 Extended functions
Parameterization
Once the bypass with synchronizer with degree of overlapping (p1260 = 1) function has
been activated, the following parameters must be set:
Table 9- 7
Parameters
r1261.0
r1261.1
p1266 =
p1269[0] =
p1269[1] =
p3800 = 1
p3802 = r1261.2
Transfer process
Figure 9-16
Signal diagram, bypass with synchronization with overlap
Transfer of motor to the line supply

 ( contactors K1 and K2 are activated by the converter):
● The initial state is as follows: Contactor K1 is closed, contactor K2 is open and the motor
is fed from the converter.
● The control bit "bypass command" (p1266) is set (e.g. by the higher-level automation).
● The bypass function sets the control word bit "synchronizing" (r1261.2).
456
Parameter settings for bypass function with synchronizer with degree of overlapping
Signal "Command switch motor - power unit"
Signal "Command switch motor - line supply"
Control signal setting
Signal source for contactor K1 feedback
Signal source for contactor K2 feedback
Synchronization is activated
Synchronizer activation is triggered by the bypass function.
Description
Operating Instructions, 07/2016, A5E00331449A
Inverter chassis units