Electrical installation
4.10 Signal connections
Fire hazard due to overheating when permissible connection cable lengths are exceeded
Excessively long connection cables connected to terminal strip X46 can cause components
to overheat with the associated risk of fire and smoke.
• Limit the length of the connecting cables to a maximum of 10 m.
• Do not route the connection cable outside the control cabinet or control cabinet group.
X400 – X402: DRIVE-CLiQ interface
Table 4- 13
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
74
WARNING
DRIVE-CLiQ interface X400 – X402: Power Module
Pin
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
Signal name
Operating Instructions, 07/2016, A5E00331449A
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply
Electronics ground
Inverter chassis units