Siemens SINAMICS G130 Operating Instructions Manual page 167

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

6. The SINAMICS drive object is detected and displayed as a bus node with IP address
169.254.11.22 and without name.
Figure 5-36
Accessible nodes
7. Mark the bus node entry and select the displayed menu item "Edit Ethernet node" with
the right mouse button.
8. In the following "Edit Ethernet node" screen, enter the device name for the Ethernet
interface ("drive1", for example) and click the "Assign name" button. Enter the IP address
(e.g. 169.254.11.10) in the IP configuration and specify the subnet screen (e.g.
255.255.255.0). Then click the "Assign IP configuration" button and close the mask.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
5.3 Procedure for commissioning via STARTER
Commissioning
167