FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
4.
----End
Follow-up Procedure
Dispose of the removed fire cylinder that is confirmed faulty.
5.4.9 Charging Extinguishant
Prerequisites
Preparations
Tools: platform scale, hose with a pressure tolerance greater than 2.5 MPa, gate valve,
camshaft device, pipe wrench, adjustable wrench
Materials: extinguishant charging cylinder with sufficient extinguishant, nitrogen cylinder
with sufficient nitrogen
Documents: fire extinguishing device installation position diagram (standard)
Skill requirement: fire engineer
Issue 04 (2018-01-05)
Figure 5-55 Removing the safety pin
Reinstall and tighten all screws.
The fire cylinder has passed the air-tightness test.
Tools and materials are ready.
All tools and materials except the camshaft device are provided by the charging station.
Extinguishant needs to be charged in the charging station.