Monitoring System - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Maintenance Item
Humidifier alarm

3.3.3 Monitoring System

Table 3-11 Quarterly maintenance checklist for the monitoring system
Item
Door status
sensor
alarms
Access
controller
Issue 04 (2018-01-05)
Operation
Check humidifier
alarms.
Expected
Method
Result
Open a door with a
The
status sensor, and
management
check the alarm
system
information
generates a
displayed on the
door status
monitoring
alarm.
software terminal.
Check the power
The power
indicator of the
indicator is
access controller.
steady red.
Check the running
The running
status indicator of
status indicator
the access
blinks white
controller.
and blue.
Check the lock
The lock status
status indicator of
indicator is
the access
steady red.
controller.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Check Standard
The humidifier has
no run overtime
alarm.
Troubleshooting
Replace the door status sensor If no
alarm is generated.
If the power indicator is off, the
power supply to the controller is
abnormal. Immediately switch off
the power input circuit breaker for
the access controller in the PDC to
prevent damaging the controller
chip. Replace the access controller.
If the running status indicator is off,
troubleshoot by following
instructions in documents delivered
with the access controller.
If the lock status indicator is off, the
electronic lock may be faulty.
Replace the electronic lock.
3 Maintenance
Troubleshooting
solution.
If the phase
current of the
humidifier is
abnormal or the
humidifier
reports a run
overtime alarm,
replace the
humidifier
cylinder by
following
instructions in
NetCol5000-A 20
kW Air-Cooled
In-Row Precision
Air Conditioner
User Manual.
24