Quarterly Maintenance; Power Supply And Distribution System - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Maintena
nce Item

3.3 Quarterly Maintenance

3.3.1 Power Supply and Distribution System

Table 3-9 Quarterly maintenance checklist for the power supply and distribution system
Item
UPS2000-G
LCD
UPS2000-G
buttons
Issue 04 (2018-01-05)
Standards
Operation
Compliance
No obvious
rubbish exists
around the
pre-fab.
module.
Check the
The ambient
temperature,
temperature,
humidity, and solar
humidity, and
radiation outside
solar radiation
the pre-fab.
meet
module.
requirements
of the
FusionModule
1000 solution
in use.
Expected
Method
Result
After you press
Press
on the
any button on
control panel.
the panel, the
LCD turns on
with a
backlight and
displays
parameters or
UPS operating
status.
Press ▲ or ▼.
All buttons
function
properly.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
If there is rubbish around the
pre-fab. module, clear the rubbish.
If the temperature, humidity, or
solar radiation outside the pre-fab.
module does not meet the project
solution requirements, contact
Huawei technical support.
Troubleshooting
If the LCD displays no information
and the backlight does not turn on,
replace the LCD. For details,
contact Huawei technical support.
If a button does not function
properly or interferes with another
button, adjust the button panel.
18