Communication Failure Alarms; Spd Alarm - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)

4.14 Communication Failure Alarms

Fault
Category
PD510
communic
ation
failure
Managem
ent system
communic
ation
failure
VCN500
communic
ation
failure
ECC500
communic
ation
failure

4.15 SPD Alarm

Fault
Category
SPD
alarm
Issue 04 (2018-01-05)
Alar
Symptom
m
Sever
ity
Major
Real-time
monitoring cannot be
performed.
Critica
Real-time
l
monitoring cannot be
performed.
Major
Real-time
monitoring cannot be
performed.
Major
Real-time
monitoring cannot be
performed.
Alar
Symptom
m
Sever
ity
Warni
The SPD module
ng
indicator is red.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
Cables are not
Verify the cable
properly
connections.
connected.
Powered on the power
distribution equipment
where the electricity
meter is installed again.
The device is
Replace the PD510
faulty.
electricity meter.
The
Refer to the section
FusionModule1
"Emergency Operations
000 is powered
for the Management
off or the circuit
System Communication
breaker has
Failure" or "Emergency
tripped.
Operations for Circuit
Breaker Tripping."
Cables are not
Verify the cable
properly
connections.
connected.
The device is
Replace the VCN500.
faulty.
Cables are not
Verify the cable
properly
connections.
connected.
The device is
Replace the ECC500
faulty.
collector.
Possible
Troubleshooting
Cause
The SPD
Replace the SPD in a
module is
PDC.
damaged by a
lightning strike.
4 Alarms and Faults
57