Huawei FusionModule 1000A40 Maintenance Manual page 170

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Figure 5-88 Removing cables from the horn strobe
Step 4 Remove screws from the horn strobe using a Phillips screwdriver, and remove the base.
Step 5 Reconnect the cables. Install the new base and cover.
Step 6 Switch on the input circuit breaker of the extinguishant control panel, and connect the battery
cables.
Step 7 Check that the new horn strobe is working properly.
1.
2.
3.
4.
----End
Follow-up Procedure
Dispose of the removed horn strobe that is confirmed faulty.
Issue 04 (2018-01-05)
While removing cables, label the cables with its corresponding terminal ports for later
connection.
As a terminal resistor is connected to the last horn strobe in the loop in parallel, remove
the terminal resistor from the faulty horn strobe, and connect the resistor to the new horn
strobe when you replace the horn strobe.
Disconnect the wiring terminals from the electrical actuator on the fire cylinder.
After the wiring terminals are disconnected from the electrical actuator, the extinguishant control panel
generates an alarm, which is normal.
Press the manual gas release button on the extinguishant control panel.
That the horn strobe is triggered indicates that the horn strobe works properly.
Reset the manual gas release button.
Flip the key to Enable Control counterclockwise (rightward). Reset the extinguishant
control panel by pressing Reset on it. Then, reset key to Enable Control clockwise
(leftward).
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Components Replacement