Replacing A Monitoring Rpdu - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Step 6 Reinstall the protective panel.
Step 7 Check that the new SPD is working properly.
----End
Follow-up Procedure
Dispose of the removed SPD module that is confirmed faulty.

5.1.3 Replacing a Monitoring rPDU

Prerequisites
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves
Materials: spare monitoring rPDU
Document: none
Skill requirement: electrician's work permit
Procedure
Step 1 Shut down devices powered by the monitoring rPDU.
Step 2 Switch off the circuit breaker of the monitoring rPDU, and unplug devices powered by the
rPDU.
Step 3 Disconnect the male connector of the monitoring rPDU from its female connector.
Step 4 Remove the monitoring rPDU using a Phillips screwdriver.
Issue 04 (2018-01-05)
A monitoring rack power distribution unit (rPDU) needs to be replaced.
A spare monitoring rPDU of the same model is available and functional.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Components Replacement