Fire Extinguishing System (Ce Kidde); Fire Extinguishing System (Ce Tyco) - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)

3.3.5 Fire Extinguishing System (CE Kidde)

Table 3-13 Quarterly maintenance checklist for the fire extinguishing system
Item
Extinguisha
nt control
panel
batteries
Hand-held
fire
extinguishe
r

3.3.6 Fire Extinguishing System (CE Tyco)

Table 3-14 Quarterly maintenance checklist for the fire extinguishing system
Device
Issue 04 (2018-01-05)
Operation
Check
Standard
1. Switch off the
1. The
power input
circuit breaker
of the
extinguishant
control panel so
that the
batteries power
the panel.
2. The battery
2. Measure the
battery voltage
using a
multimeter.
Check the
The hand-held
hand-held fire
fire
extinguisher.
extinguisher is
in good
condition.
The pressure
pointer of the
hand-held fire
extinguisher is
in the green
zone.
The hand-held
fire
extinguisher is
within the
validity period.
Operation
Check Standard
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting
Replace batteries for the
extinguisha
extinguishant control panel.
nt control
panel
reports a
power
supply
fault.
voltage is
24± 1 V
DC.
Replace the hand-held fire
extinguisher.
Replace the hand-held fire
extinguisher.
Replace the hand-held fire
extinguisher.
3 Maintenance