Huawei FusionModule 1000A40 Maintenance Manual page 175

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Figure 5-92 Removing the base
Step 5 Install the new extinguishant abort button panel in the same way.
Step 6 Connect the cables to the panel of the new extinguishant abort button. Connect cables to the
correct terminals.
Step 7 Install the new extinguishant abort button panel in the same way.
Figure 5-93 Installing the extinguishant abort button
Step 8 Switch on the input circuit breaker of the extinguishant control panel, and connect the battery
cables.
Step 9 Check whether the new extinguishant abort button is working properly.
1.
After the wiring terminals are disconnected from the electrical actuator, the extinguishant control panel
generates an alarm, which is normal.
Issue 04 (2018-01-05)
Disconnect the wiring terminals from the electrical actuator on the fire cylinder.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Components Replacement
167