Procedure
Step 1 (Optional) Use the ESD floor suction plate to open the aisle floor where a humidifier water
refill pipe needs to be replaced.
Step 2 Close the control valve of the humidifier water refill pipe that leaks, and remove the thermal
insulation foam.
Step 3 Remove the water inside the pre-fab. module using a sucker and vessel.
Step 4 Remove the leaking water refill pipe, and drain the residual water in the pipe to the vessel.
Step 5 Install a new water refill pipe.
Check that the safety clamp is secured and that the water pipe does not leak.
Step 6 Open the control valve of the water refill pipe, wait until the new pipe is working properly,
and wrap the new pipe with a thermal insulation layer.
Step 7 (Optional) Reinstall the aisle floor.
----End
Follow-up Procedure
Dispose of the removed humidifier water refill pipe that is confirmed faulty.

5.2.6.2 Replacing the Condensate Drainpipe of a Precision Air Conditioner

Prerequisites
Impact on the System
None
Preparations
Tools: adjustable wrench, utility knife, flat-head screwdriver, protective gloves, ESD floor
suction plate, vessel, sucker
Materials: dry rag, rubber plug, thermal insulation foam, spare condensate drainpipe
Document: pre-fab. module layout diagram
Issue 04 (2018-01-05)
For the diagrams, see the quick installation guide for the solution in use.
Wipe off the water with a dry cloth if there is not much water.
A condensate drainpipe needs to be replaced.
A spare condensate drainpipe of the same model is available and functional.
Huawei Proprietary and Confidential