Emergency Operations For Circuit Breaker Tripping; Emergency Operations For Overload - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Step 3 Monitor the system running until the mains supply is stored and the system is working
properly.
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.

6.2 Emergency Operations for Circuit Breaker Tripping

Prerequisites
A circuit breaker has tripped.
Procedure
Step 1 Promptly locate the control range of the circuit breaker that has tripped.
Step 2 Analyze the cause of the circuit tripping and switch on the circuit breaker as soon as possible.
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.

6.3 Emergency Operations for Overload

Prerequisites
An overload alarm is generated.
Procedure
Step 1 Locate the cable or device based on the alarm information.
Step 2 Check the overloaded cable or device and locate the fault.
----End
Issue 04 (2018-01-05)
If the ATS switchover fails, manually switch the ATS to the other mains or DG supply,
and check whether all devices are working properly.
Important devices of the FusionModule1000 are powered by two power supplies. If one circuit breaker
trips, it does not affect the operation of importance devices. However, the situation needs to be handled
promptly to avoid jeopardizing the long term stable running of the equipment.
If the cable or device is seriously overloaded, immediately power off the device and its lower-level
devices.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Emergency Operations
178