Huawei FusionModule 1000A40 Maintenance Manual page 19

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Item
air-cooled
precision
air
conditioner
s
Screws
securing the
compressor
of the 20
kW
air-cooled
precision
air
conditioner
Service
valves of
the 20 kW
air-cooled
precision
air
conditioner
s
Compressor
running
sound of
the 20 kW
air-cooled
precision
air
conditioner
Evaporators
of the 20
kW
air-cooled
precision
air
conditioner
s
Refrigerant
pipes of the
20 kW
air-cooled
precision
air
conditioner
s
Issue 04 (2018-01-05)
Expected
Method
Result
The air filters
are not
damaged or
misshapen.
Check screws
The
securing the
compressor
compressor.
screws are
secure.
Check the
The
compressor service
compressor
valves.
service valves
have no oil
stains.
Listen to the
No abnormal
compressor
noise is
running sound.
generated.
Check the
No foreign
evaporators.
matter exists
on the
evaporator
surfaces.
Check the
The refrigerant
refrigerant pipes.
pipes do not
leak, are not
corroded, and
are properly
wrapped with
thermal
insulation
foam.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
If an air filter is damaged or
misshapen, replace air filters for a
20 kW air-cooled precision air
conditioner.
If a compressor fan screw is loose,
tighten the screw.
If a compressor service valve is
covered by oil stains, clean the oil
stains.
If the compressor generates
abnormal noise, replace the
compressor by following
instructions in NetCol5000-A 20 kW
Air-Cooled In-Row Precision Air
Conditioner User Manual.
If an evaporator is covered by
foreign matter, clean the foreign
matter.
In the case of pipe leakage, pipe
corrosion, or thermal insulation
foam damage, repair the leakage
and corrosion, and rewrap the
thermal insulation foam.
11