Maintenance Guide (2016.05, AI Version)
Item
Door
opening
function of
the access
control
system

3.2.4 Fire Extinguishing System (Standard)

Table 3-5 Monthly maintenance checklist for the fire extinguishing system
Device
Fire alarm
control
panel
Batteries of
the fire
alarm
control
panel
Issue 04 (2018-01-05)
Method
Swipe an access
card outside the
pre-fab. module to
open the module
door.
Press the exit
button inside the
pre-fab. module to
open the module
door.
If the pre-fab. module door cannot be opened from inside the module using the exit button, you can exit
from the module using the emergency door.
Operation
Check indicators
on the fire alarm
control panel.
Check whether the
battery wiring
terminals are
corroded.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Expected
Troubleshooting
Result
After you
If the module door cannot be
swipe the card,
opened, swipe another access card
the indicator
and observe the door status:
on the card
If the door can be opened by
reader turns on
another access card, the original
in red for 3s,
access card is damaged. Prepare
and changes
a new access card and assign
back to steady
permission to the card.
blue.
If the door still cannot be
Meanwhile,
opened, open the door using the
you can hear a
emergency door release button,
beep sound.
and check whether the electronic
The module
lock or card reader is normal.
door can be
Replace the end door card reader
opened by
if it is faulty.
turning the
handle.
The module
Replace the exit button if the
door can be
module door cannot be opened.
opened after
you press the
exit button.
Check
Troubleshooting
Standard
The power
Replace the fire alarm control panel.
indicator turns
on, and the
alarm indicator
turns off.
The wiring
Clean the contaminated and
terminals are
corroded terminals. Replace the
in good
batteries with severely corroded
condition
terminals for the fire alarm control
without
panel.
corrosion.