Kw Air-Cooled Precision Air Conditioner Alarms - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Fault
Category

4.18 20 kW Air-Cooled Precision Air Conditioner Alarms

Fault
Category
Issue 04 (2018-01-05)
Alarm
Severity
Major
Major
For other UPS2000-G alarms, see UPS2000-G-(6 kVA-20 kVA) User Manual.
Alarm
Severity
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Symptom
Possible Cause
Abnormal
The UPS is faulty.
noise or
smell is
generated
in the UPS
cabinet.
The battery
The UPS will
indicator
soon shut down
blinks. The
due to low
buzzer
battery, and loads
buzzes. The
will be powered
battery
off.
capacity is
insufficient,
and the
UPS is
shutting
down.
The number of
batteries or the
battery capacity is
incorrectly set.
Symptom
Possible
Cause
4 Alarms and Faults
Troubleshootin
g
Shut down the
UPS and cut off
the power input
immediately.
Contact Huawei
technical support.
Save data and
shut down
primary loads
immediately to
avoid data loss or
corruption.
Connect the UPS
input to the
backup AC power
supply
immediately.
Verify that the
number of
batteries and
battery capacity
are correctly set
based on the
actual
configuration, and
that the settings
are consistent
with the initial
configuration
requirements in
UPS2000-G-(6
kVA-20 kVA)
User Manual and
the initial
configuration
parameter
manual.
Troubleshooti
ng
60