FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Maintenance Item
Screws securing the
indoor fan of the 20
kW air-cooled
precision air
conditioner
Air filters of the 20
kW air-cooled
precision air
conditioners
Condensate pan and
floats of the 20 kW
air-cooled precision
air conditioner
Issue 04 (2018-01-05)
Operation
Check screws
securing the indoor
fan.
Check the air filters.
Check the
condensate pan and
floats.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Check Standard
The indoor fan
screws are secure.
The filters are clean
and not blocked.
The air filters are
not damaged or
misshapen.
The condensate pan
and floats are free
from scale.
3 Maintenance
Troubleshooting
If an indoor fan
screw is loose,
tighten the screw.
If an air filter is dirty
or blocked, remove
dust from the air
filter using a brush
or vacuum cleaner.
Replace any
damaged or
misshapen air filters
for a 20 kW
air-cooled precision
air conditioner.
If there is scale on
the condensate pan
and floats, clean the
condensate pan and
floats.