Safety Devices - Fujitsu Airstage J-II Series Design & Technical Manual

Small vrf system
Table of Contents

Advertisement

9. SAFETY DEVICES

Model and type
AUUA4TLAV1
AUUA7TLAV
AUUA9TLAV
Compact cassette
AUUA12TLAV
AUUA14TLAV
AUUA18TLAV
AUUA24TLAV
AUUB18TLAV1
AUUB24TLAV1
AUUB30TLAV1
Circular flow cassette
AUUB36TLAV1
AUUB48TLAV1
AUUB18TLAV
Cassette
(Slim type)
AUUB24TLAV
AUUB30TLAV
Cassette
AUUB36TLAV
Mini duct
ARUL4TLAV1
ARUL7TLAV
ARUL9TLAV
Slim duct / slim
ARUL12TLAV
concealed floor
ARUL14TLAV
ARUL18TLAV
ARUM24TLAV
Medium static
pressure duct
ARUM30TLAV
ARUM36TLAV
1
*
: Fuse for fan motor.
2
*
: Including in the Drain Pump Unit (Optional parts)
Fan motor thermal
Fuse
protector
Activate at
280.4±27°F
(138±15°C):
250V
Fan motor stop
Reset at
3.15A
221±36°F
(105±20°C):
Fan motor restart
Activate at
257±18°F
(125±10°C):
250V
Fan motor stop
Reset at
3.15A
248±18°F
(120±10°C)
Fan motor restart
Activate at
+27
230
°F
-18
+15
(110
°C):
-10
250V
Fan motor stop
Reset at
3.15A
+27
221
°F
-18
15
(105+
°C):
-10
Fan motor restart
Activate at
275±27°F
(135±15°C):
250V
Fan motor stop
Reset at
3.15A
239±27°F
(115±15°C):
Fan motor restart
Activate at
275±27°F
(135±15°C):
250V
Fan motor stop
Reset at
5A
239±27°F
(115±15°C):
Fan motor restart
Activate at
275±27°F
(135±15°C):
Fan motor stop
Reset at
239±27°F
(115±15°C)
250V
Fan motor restart
Activate at
5A
239±27°F
(115±15°C):
Fan motor stop
Reset at
158°F or less
(70°C or less):
Fan motor restart
- (04-225) -
Terminal
Float
thermal fuse
switch
2
*