Fujitsu Airstage J-II Series Design & Technical Manual page 618

Small vrf system
Table of Contents

Advertisement

„ CIRCULAR FLOW CASSETTE TYPE / CASSETTE TYPE
11 in. (300 mm)
Downward
or less
slope1/100 or
more
ø3/4 [I.D.] ; ø1-1/16 [O.D.]
drain hose
(Locally purchased)
(accessory)
Attached band
Air vent
Rise
● Drain lift-up pipe restrictions:
(1) Lift-up height ≤ 33 in.
(2) Drain hose (pipe) length ≤ 11 in. (300 mm) (between indoor unit and lift-up pipe)
● Water leakage may result from a failure to adhere to the restrictions above.
ø3/4 [I.D.] ; ø1-1/16 [O.D.]
Horizontal or
upward slope
Prohibited
Trap
850 mm) (from ceiling)
(
- (06 - 54) -
60 to 78 in. (1.5 to 2.0 m)
Downward slope 1/100 or more
Pipe Hanger

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage aou36rlavmAirstage aou48rlavmAirstage aou60rlavmAirstage auua4tlav1Airstage auua7tlavAirstage auua9tlav ... Show all

Table of Contents