„ SYSTEM DIAGRAM
z Multiple remote control
Up to 4 remote controllers can be used to operate the indoor units.
I.U.
A
Master
A, B, C, D : Remote controller cable. (Refer to Chapter6. 4-4 for detail specifications)
A≤1,640 ft. (500 m), A+B≤1,640 ft. (500 m), A+B+C≤1,640 ft. (500 m), A+B+C+D≤1,640 ft. (500 m).
NOTE: Multiple installation method described above is prohibited to combine with UTY-RNKU (3 Wired
type) or UTY-RSKU (3 Wired type) or UTY-RHKU (3 Wired type) and UTY-RNRUZ1 (2 Wired
Type)
z Group control
With a single remote controller, up to 16 units can be simultaneously operated.
I.U.
I.U.
B
A
Master
A, B, C, D, E : Remote controller cable. (Refer to Chapter6. 4-4 for detail specifications)
A+B+C+D+E≤1,640 ft. (500 m).
I.U.
A
B
A
Master
Slave
Master
I.U.
C
D
E
- (05 - 59) -
I.U.
I.U.
B
C
A
Slave
Slave
Master
I.U.
B
C
D
Slave
Slave
Slave