„ SLIM DUCT / SLIM CONCEALED FLOOR TYPE
z Ceiling concealed setting
Drain cap
Arrange the drain hose
lower than this position
Trap
Locally purchased
Max.
11 in.
(300 mm)
Horizontal or
upward slope
z Floor standing concealed setting
Drain cap
● Install the drain pipe with downward slope (1/50 to1/100) and so there are no rises or traps in the pipe.
● Use general hard polyvinyl chloride pipe (ø3/4 [I.D.] ; ø1-1/16 [O.D.]) and connect it with adhesive (polyvinyl
chloride) so that there is no leakage.
● Install pipe supports on long lines.
● Do not install air vents on the drain lines.
● Always insulate the drain pipe to prevent condensation.
Drain hose
Prohibited
Rise
Gap of 60 to 79 in. (1.5-2.0 m)
Pipe
Supporters
ø3/4 [I.D.] ;
ø1-1/16 [O.D.]
27 in.
(700 mm) or less
Prohibited
Trap
- (06 - 56) -
Supporter
60 to 79 in.(1.5 to 2.0 m)
Air vent
Prohibited
Air vent
Trap
Rise
Rise