Fujitsu Airstage J-II Series Design & Technical Manual page 863

Small vrf system
Table of Contents

Advertisement

2 (In-line connection)
●Example
Indoor unit fan operation status use
External output: Heating thermostat ON
External output 3: Indoor unit fan operation status
Humidifier
3 (In-line connection)
●Example
Disable cool air prevention function.
The indoor unit fan is operated at the set speed continuously.
External output: Heating thermostat ON
Humidifier
The Heating thermostat output for CNB01 (1-2 or 1-3 or 1-4 or 1-5) will be ON when EEV ON or external heater
ON.
The Heating thermostat output will be OFF when EEV OFF and external heater OFF.
Heating operation
Heating thermostat
ON output
EEV ON / OFF
External heater
output ON / OFF
43-00
Fan
43-01
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Cool air prevention
OFF