2-16-2. MODEL: UTY-VGGXZ1
SWITCH POSITION
● Set network convertor rotary switch SW110 and SW111.
REFRIGERANT CIRCUIT ADDRESS SETTING
For Split system
z Example
Refrigerant
circuit
Rotary SW110
address
(10 digit)
01
99
*Setting range 00 - 99 (Arbitrary numbers can be set)
*When connecting the Network convertor for Single split AC , set up the number so that the Refrigerant circuit ad-
dress number of outdoor unit and indoor unit does not overlap .
And the sum total of the Refrigerant circuit address of Network convertor for Single split AC and the Refrigerant
circuit address of VRF outdoor units and the indoor unit is a maximum of 100.
SW110 SW111
Network convertor PCB
SW setting
Rotary SW111
(1 digit)
0
1
9
9
- (07 - 134) -