Fujitsu Airstage J-II Series Design & Technical Manual page 724

Small vrf system
Table of Contents

Advertisement

LED105
Setting Mode
CODE No.
Outdoor
temperature
zone boundary
3
7
temperature
B
Capacity
priority setting
4
0
(in low noise
mode)
Low noise
4
1
mode setting
4
2
Prohibited
6
0
Prohibited
6
1
Prohibited
6
2
Prohibited
LED104
Setting Function
CODE No.
0
0
42.8°F (6°C)
0
1
14.0°F (-10°C)
0
2
17.6°F (-8°C)
0
3
21.2°F (-6°C)
0
4
24.8°F (-4°C)
0
5
28.4°F (-2°C)
0
6
32.0°F (0°C)
0
7
35.6°F (2°C)
0
8
39.2°F (4°C)
0
9
42.8°F (6°C)
1
0
46.4°F (8°C)
1
1
50.0°F (10°C)
1
2
53.6°F (12°C)
1
3
57.2°F (14°C)
1
4
60.8°F (16°C)
1
5
64.4°F (18°C)
0
0
Off (quiet priority)
0
1
On (capacity priority)
0
0
Off (Normal)
0
1
On (Low noise mode)
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
- (07 - 77) -
Factory
Remarks
setting
l
Setting required if changing of the outdoor
temperature setting for heat pump only zone is
required when heater selection control using
outdoor temperature 1 is performed on the
indoor unit.
For details, refer to Chapter 8. 1-2-2.
EXTERNAL OUTPUT.
If the cooling/heating performance becomes
l
insufficient when the low noise mode is set,
it is possible to set "capacity priority" that
automatically cancels the low noise mode
(once performance is restored, the mode will
automatically return to the low noise mode).
l
l
Setting prohibited
l
Setting prohibited
l
Setting prohibited
l
Setting prohibited