Fujitsu Airstage J-II Series Design & Technical Manual page 689

Small vrf system
Table of Contents

Advertisement

z Refrigerant circuit address setting
9) Pressing the SET TEMP. p button or SET TEMP. q button, select a remote controller
address (select the indoor unit you want to operate).
*If the indoor unit you want to operate has already been selected, skip step 9).
10) Press the FAN button so that the "Function number" display flashes. Then, press either
the SET TEMP. p button or the SET TEMP. q button to display function number "02."
11) Press the FAN button so that the "Setting number" display flashes. Then, press either the
SET TEMP. p button or the SET TEMP. q button to set up the refrigerant circuit address
data. (The setting range is from 00 to 99.)
12) Pressing the START/STOP button, confirm the selected refrigerant circuit address data.
(The data will be transferred to the indoor unit.)
● When refrigerant circuit address data was not
set up on the indoor unit (-- is displayed.)
● Set up refrigerant circuit address data again
according to the procedure in step 11) above.
Remote controller address
Ex.) When remote controller address "01" is selected
Function number
Refrigerant circuit address data
Ex.) When refrigerant circuit address data "18" is set up
ERROR
When refrigerant circuit address data was
normally set up on the indoor unit.
- (07 - 42) -
GOOD