Fujitsu Airstage J-II Series Design & Technical Manual page 780

Small vrf system
Table of Contents

Advertisement

2-16. NETWORK CONVERTOR
2-16-1. MODEL: UTY-VTGX
„ SWITCH POSITION
● Set network convertor rotary switch SET1, and Dip switch SET2, SET3.
„ REFRIGERANT CIRCUIT ADDRESS SETTING (SET 1)
z Example
Refrigerant
circuit
SET1 (x10)
address
(10 digit)
01
99
*Setting range 00 - 99 (Arbitrary numbers can be set)
*When connecting the Network convertor for Single split AC , set up the number so that the Refrigerant circuit ad-
dress number of outdoor unit and indoor unit does not overlap .
And the sum total of the Refrigerant circuit address of Network convertor for Single split AC and the Refrigerant
circuit address of the outdoor unit and the indoor unit is a maximum of 100.
„ TERMINAL RESISTER SETTING (SET 2)
Set to "ON" when there is no termination resistance in the segment separated by the signal amplifier.
(Default: OFF)
„ REMOTE CONTROLLER 2WIRE/3WIRE SWITCHING (SET 3)
Match with the setting of the used indoor unit.
Set matched with the connection method of the remote controller cable to be connected.
(Default: 2WIRE)
SW setting
SET1 (x1)
(1 digit)
0
1
9
9
- (07 - 133) -