Fujitsu Airstage J-II Series Design & Technical Manual page 399

Small vrf system
Table of Contents

Advertisement

Item
Others
External input/output
● When Start/Stop, operation mode setting, room temp. setting, fan speed setting, airflow direction setting, swing
setting, economy mode, and anti freeze setting are changed frequently by using the central controller like System
Controller, Touch Panel Controller, etc. or from Building Management System (BMS) via BACnet
Network Convertor, the number of operations for each indoor unit must not exceed 7,500 times/year.
If the number of setting change exceeds the above specified number, the rewriting count limit of the non-volatile
memory (memory built into the air conditioner and used for recording settings) will be exceeded, and may cause
breakdown.
1
*
: Product specifications are subject to change without notice.
2
*
: Option
Main unit
PC / Tablet
Input: Batch operation/stop, emergency stop, electricity meter
z
Output: Operation monitoring, error
- (05 - 36) -
Description
Gateway or via
®