„ MAXIMUM WIRING LENGTH OF VRF NETWORK SYSTEM
Transmission line
Total wiring length of transmission
Maximum wiring length between units
Total wiring length in 1 segment *
Wiring length [ft (m)]
Number of unit
¾ Segment: Refer to „ MAXIMUM CONNECTION OF NETWORK SEGMENT for network
segment figure and explanation.
„ THE MAXIMUM CONNECTABLE UNIT
z Outdoor unit and indoor unit
Outdoor unit
Indoor unit
VRF network system
11,811 (3,600)
400
Maximum connectable units in
one VRF network system
100
400
- (06 - 04) -
Maximum wiring length
ft. (m)
11,811 (3,600)
1,312 (400)
1,640 (500)
segment *
1,640 (500)
64