Fujitsu Airstage J-II Series Design & Technical Manual page 850

Small vrf system
Table of Contents

Advertisement

-2: Economizer 2, 3 (Cooling 2 stage output + occupied)
In / Out Mode 3 or 4 (60-03 or 04)
Function
Mode
setting
60-03
3
60-04
4
Occupied / Unoccupied status *1
Office
Fri 10:00AM
Mode
Set Temp.
Fan
Custom
Cool
80°F
Auto
Auto
74°F
Heat
Cool
84°F
Room Temp.
Away
76°F
Heat
68°F
Vacation
Status
Menu
Wired remote controller
*1. By the Wired remote controller (Touch panel), external output indication is transferred to Economizer logic mod-
ule through the indoor unit.
● Economizer Logic module is required for Economizer operation.
● Economizer Logic module judges the amount of outdoor air intake depending on indoor unit output at operating
condition, occupied status and outdoor temperature etc.
● Cooling operation by only free cooling is possible.
Operation
Operating Mode
VRF
Indoor unit
Mechanical
Cooling ON
Cooling Low
Mechanical
Cooling ON
Cooling High
Cooling
Free Cooling only
OFF
Mechanical & Free
Cooling ON
Cooling
Cooling
Cooling
Thermostat
OFF
OFF or Heating
Cooling
OFF
OFF
*2. Indoor unit decides the cooling high/low based on the set temperature and the indoor temperature.
*3. When external output by remote controller is OFF, the amount of intaken fresh air differs as follows:
- Cooling by intaken fresh air is performed: None to Maximum amount
- Cooling by intaken fresh air is not performed: None
External input
CNB01
(PIN 1-2)
CNA03 or
[Cooling
CNA04 (EXT.
thermostat ON]
IN2)
CNB01
[VRF cooling
(PIN 1-2)
ON]
[Cooling
thermostat ON]
Remote controller output
(Occupied / Unoccupied status)
Indoor unit
Condition
(Enthalpy or Temp.)
Damper
(Free
Outdoor
Return
Cooling)
OFF
High
Low
OFF
High
Low
ON
Low
High
ON
Low
High
OFF
-
-
OFF
-
-
- (08 - 30) -
External output
CNB01
(PIN 1-3)
[Cooling high /
low output]
controller output]
CNB01
(PIN 1-5)
[Cooling high /
low output]
controller output]
Cooling thermostat ON
(Cooling 1)
Cooling high / low output
(Cooling 2)
Economizer logic module
VRF cooling ON
(Economizer input)
Indoor unit output
Cooling
Cooling
Occ/Unocc
Thermostat
High/Low*2
(RC output)
ON
ON
OFF(Low)
ON(Occ)
ON
ON(High)
ON(Occ)
ON
OFF(Low)
ON(Occ)
ON
ON(High)
ON(Occ)
OFF
OFF
ON(Occ)
OFF
OFF
OFF(Unocc)
Remote controller
CNB01
(PIN 1-4)
[Remote
UTY-RNRU
Occupied/
Unoccupied
CNB01
status
(PIN 1-4)
[Remote
Indoor unit
Input
Outdoor air
intake*3
VRF
Cooling ON
ON
Minimum
ON
Minimum
Modulating
OFF
(Min-Max)
Modulating
ON
(Min-Max)
OFF
Minimum
OFF
None