Fujitsu Airstage J-II Series Design & Technical Manual page 468

Small vrf system
Table of Contents

Advertisement

„ WIRING SPECIFICATIONS
Use
Power cable (using
remote control
cable)
Transmission cable
: Use shielded cable in accordance with local rules for remote controller cable.
NOTE: Select a flexible cable that can be bound using cable ties from over the cable sheath inside this product.
● Maximum connectable number of remote controllers by cable size and length:
Cable size
AWG
mm²
16
1.25
0.75
18
(1.25 > S* ≥ 0.75)
0.5
20
(0.75 > S* ≥ 0.5)
0.3
22
(0.5 > S* ≥ 0.3)
NOTE: Cable size and length conditions within the remote controller group this product is connected:
Size and length of the cable connected to this product should be included.
Size
16 to 22 AWG
Non-polar 2 core, twisted
(0.33 to 1.25
mm²)
pair sheathed PVC cable
22AWG LEVEL 4 (NEMA)
22 AWG
non-polar 2core, twisted
(0.33 mm²)
pair solid core diameter
0.65mm
Maximum connectable number of remote controllers
L* ≤ 100 m
2
2
2
2
- (05 - 105) -
Cable type
Maximum cable length:
32ft (10m)
L
ON
cable
100 m < L* ≤ 250 m 250 m < L* ≤ 500 m
2
2
Prohibited
Remarks
®
W
compatible
ORKS
2

Hide quick links: