Fujitsu Airstage J-II Series Design & Technical Manual page 761

Small vrf system
Table of Contents

Advertisement

Function
Function
number
00
*1 Auto mode
68
type
01
00
01
02
03
04
*1 Deadband
69
value
05
06
07
08
09
*1 : Function number 68 and 69 will be usable provided that the corresponding operating device is connected.
Setting number
Default
Single
setpoint
auto
mode
(traditional)
Dual setpoint
auto
mode
0°C
0.5°C
1.0°C
1.5°C
2.0°C
2.5°C
3.0°C
3.5°C
4.0°C
4.5°C
- (07 - 114) -
Switch the setting method of auto mode to single or dual (cooling/
heating).
For heat pump systems, it is necessary to set the master indoor unit (by
wired remote controller).
Choose the minimum temperature between cooling and heating
settings (deadband) for Dual setpoint auto mode (set in No. 68).
Details