To protect the compressor of the outdoor unit, carefully read and understand the following cautions that may affect
the operation of the compressor before executing the setting.
When performing periodical settings like schedule settings for the following functions, perform the setting to all the
indoor units in the same refrigerant system simultaneously, conforming to the timing restriction described below.
<Corresponding function>
· Start operation
· Release indoor unit forced
thermostat off mode
Forced thermostat OFF instruction
Only one equipment can send these instructions for each refrigerant system.
When these instructions are sent by multiple equipment, the system may not respond as instructed or may
malfunction.
SPECIFICATIONS
Power supply
Input Power (W)
Temperature: °F (°C)
Humidity (%)
Dimensions [H × W × D]: in. (mm)
Weight: lbs. (g)
z Transmission specifications
Transfer mode
Communication method
Communication speed
Synchronous system
Data bit
Parity
Stop bit
Network
Maximum cable length
More than 10 minutes must elapse
More than 10 minutes must elapse
1ø AC 208-240 V 50/60 Hz
Operating
32 to 114.8 (0 to 46)
Packaged
14 to 140 (-10 to 60)
Packaged
2-1/8 × 10-1/4 × 5-7/8
RTU mode
Half-duplex operation, Master/slave method
9,600bps / 19,200bps
Asynchronous communication method
8 bit
even/odd/none
2 bit (no parity) / 1 bit
3 wire RS485
3,280 ft. (1,000 m)
- (05 - 130) -
· Stop operation
· Set indoor unit forced thermostat
off mode
2.0
0 to 95 (RH) ;
No condensation
(54 × 260 × 150)
2 (1,100)