Siemens SINAMICS S120 Manual page 175

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

LED
Color
F_DI z
LED
LED
(input x, (x
x
x+1
+1)+, (x
Red
+1)-)
Red
LED
LED
x
x+1
Green
Green
Green
Green
Single digital inputs, not fail-safe
DI x
Green
Fail-safe digital outputs with associated readback channel
F_DO y
Green
(0+..3+,
0-..3-)
Readback input DI 2y for output F_DO y (y = 0 ... 3) for test stop.
The status of the LEDs also depends on the type of external circuit.
DI 2y
Green
Inputs x+1 (DI 1+, 3+, .. 19+) can be set individually by parameter p10040 (TM54F).
1)
p10040 (TM54F) = 0: Input x+1 is an NC contact.
p10040 (TM54F) = 1: Input x+1 is an NO contact.
Factory setting: p10040 (TM54F) = 0 for all inputs x+1.
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2
Status
NC contact/NC contact
Continuous
Different signal states at input x and x+1
light
Off
No signal at input x and no signal at input x+1
NC contact/NO contact
Continuous
Same signal states at input x and x+1
light
Off
No signal at input x and no signal at input x+1
NC contact/NC contact
Continuous
One signal at input x and one signal at input x+1
light
NC contact/NO contact
Continuous
One signal at input x and no signal at input x+1
light
Off
No signal at digital input x (x = 20 ... 23)
Continuous
Signal at digital input x
light
Continuous
Output y (y = 0 ... 3) has an active signal
light
Off
One of the two output lines y+ or y- or both lines of output
y carry a signal
Continuous
Both output lines y+ and y- carry no signal
light
6.6 Terminal Module TM54F
Description, cause
1)
: (z = 0 ... 9, x = 0, 2, ... 18)
1)
: (z = 0 ... 9, x = 0, 2, ... 18)
1)
: (z = 0 ... 9, x = 0, 2, ... 18)
1)
: (z = 0 ... 9, x = 0, 2, ... 18)
Terminal Modules
Remedy
173