6.6.2.10

X531 fail-safe digital inputs and dynamically adjustable power supply

Table 6-41
X531: Fail-safe digital inputs
Terminal
1
2
3
4
5
6
7
8
An F-DI consists of 1 digital input and a 2nd digital input where, in addition, the cathode of the optocoupler is fed-out.
F-DI 5 = terminals 2, 3 and 6
F-DI 6 = terminals 4, 5 and 7
Type: Screw terminal 1 (Page 321)
DI: Digital input, F-DI: Fail-safe digital input
1)
Pure hardware delay
2)
Note
Execution of a test stop
The test stop of the F-DI 5 to F-DI 9 can only be performed if the F-DI is supplied from L2+.
Note
Ensuring the function of digital inputs
For the digital inputs DIx+ to function, the reference potential must be connected to input DIx-
in each case.
This is achieved by using one of the following measures:
1. Providing the ground reference of the digital inputs
2. A jumper between DIx- and terminal M1
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2
Designation
1)
L2+
DI 10
F-DI 5
DI 11+
DI 12
F-DI 6
DI 13+
DI 11-
F-DI 5
DI 13-
F-DI 6
M1
6.6 Terminal Module TM54F
Technical data
Switched voltage: +24 V DC
Max. total load current: 500 mA
(voltage is switched for a test stop)
Voltage: -3 ... +30 V DC
Electrical isolation: Yes
Reference potential: see terminals 6, 7, 8
Input characteristic acc. to IEC 61131-2, type 1
Input voltage (including ripple)
"1" signal: 15 ... 30 V
"0" signal: -3 ... +5 V
Input current
at 24 V DC: typ. 3.2 mA
at <0.5 mA: Signal "0" reliably detected
Input delay:
2)
for "0" → "1": typ. 30 μs
for "1" → "0": typ. 60 µs
Switching frequency: max. 100 Hz
Reference potential to DI 11+
Reference potential to DI 13+
Reference potential to DI 10, DI 12, L2+