Encoder system connection
9.7 Sensor Module Cabinet-Mounted SMC40
Removal
1. First shift the mounting slide downwards at the lug to release the interlocking with the
mounting rail.
2. Swivel the component to the front and withdraw it upwards from the DIN rail.
Figure 9-27
Mounting clearances
The SMC40 can be installed in the line-up together with other SMCs as required. When mounting
next to heat sources, the following minimum lateral clearances must be observed:
• 50 mm for Line Modules and Motor Modules
• 100 mm for hotter components (e.g. pulsed resistor)
274
Mounting slide
Mounting rail
Removing from a DIN mounting rail
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2