LED INDICATION

LED
NORMAL
RUN
Flash
(120 IPM)
CRC
Off
PCM
Off
FRM
Off
RMT
Off
AIS
Off
Alarm Indications on 24DTI
FAULT
CAUSE
On or Off
Abnormal opera-
tion of DTI card
On
Bit Error Rate
exceeds the prede-
termined value
On
No PCM signals
arrive from the dis-
tant office
On
Frame Alignment
signals from the
distant office can-
not be received
On
Frame Alignment
signals cannot be
sent to the remote
PBX
On
Remote PBX is in
the local loopback
state
– 317 –
CHAPTER 5 OPERATION TEST
INTEROFFICE TRANSMISSION LINE TEST
FAULT
ACTION
1
Confirm the programming data:
CM05 Y=0/Y=1, CM07 Y=01.
2
Check to see if the SENSE switch
is set as per the AP number (04-
15, 20-31) assigned by CM05
Y=0.
3
Reset the MB switch
(Down→Up→Down)
If the fault cannot be cleared,
4
replace the card.
1
Check the receive line and exter-
nal equipment.
2
Replace the remote DTI card.
1
Check to see if the line is correctly
connected to the DTI card.
2
Plug and unplug the DTI card.
Repeat this two or three times.
1
Check the receive line and exter-
nal equipment.
2
Replace the remote DTI card.
Check the transmission line and
1
external equipment.
2
Replace the DTI card.
Check the switch settings of the remote
DTI card.
NWA-008852-001 Rev.5.0
98ch5001.fm