Communication PROFIBUS DP/PROFINET IO
10.1 Communication according to PROFIdrive
● S7 protocol
● PROFIdrive parameter channel with the following data sets:
Figure 10-19 Reading and writing data
472
This protocol uses the STARTER commissioning tool, for example, in online mode via
PROFIBUS.
– PROFIBUS: Data block 47 (0x002F)
The DPV1 services are available for master class 1 and class 2.
– PROFINET: Data block 47 and 0xB02F al global access, data set 0xB02E as local
access
Note
Please refer to the following documentation for a detailed description of acyclic
communication:
Reference: PROFIdrive Profile V4.1, May 2006, Order No: 3.172
Addressing:
PROFIBUS DP, the addressing can either take the form of the logical address or the
diagnostics address.
PROFINET IO, addressing is only undertaken using a diagnostics address which is
assigned to a module as of socket 1. Parameters cannot be accessed via socket 0.
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5